Introducing the LeveleseTM LS-200/CS-100 Single and Dual Fuel Overfill Level Sensor and Control Station, consisting of of a dual point level sensor with adjustable set points and an electronic Control station with audible and LED visual alarm and shut-off valve control.
The LeveleseTM LS-200/CS-100 has been specifically designed to accurately and repeatably guage diesel engine tanks ranging in depth from 6 inches and switch on (1) a high level alarm and (2) a shutoff alarm and valve shutoff when levels reach near overflow conditions. Features include:
- Independently-Adjustable Dual Float Operated Level Switches with 2” NPT Mounting and NEMA-4X Enclosure
- Level Sensor Pressure Sealed to Prevent Leaks
- Electromechanical Controls with Barrier Strip Termination
- Surface Mount NEMA-4X Electronics Enclosure
- Universal 12 or 24 VDC Power
- Designed to meet the requirements of NFPA-30.
HOW IT WORKS
The LS-200 Dual Level Alarm uses two magnetic floats, one for alarm and the other for shut-down, each operating an ndependent, hermetically sealed reed switch activated when the float passes the sensitive portion of the switch. When the fuel level reaches a preset point, the switch changes state. Each switch is rated at 1 Amp, 117 VAC, is mounted on a HDPE tube, passes a leak test of more than 100 psig, is independent from the other and may be field adjusted by moving the HDPE tube and setting it with a set screw.
|
Contact us
Telephone: 303-586-1890
Email: info@levelese.com
|
|
Designed to meet the requirements of NFPA-30, the LS-200/-CS100 Control Station is a hardened electronic or electromechanical circuit mounted in a NEMA-4X housing. When the alarm level switch is closed, it activates a large Amber LED and Sonalert audible alarm. When the level reaches the Shut-down point, it removes power for the fill pipe solenoid valve, shutting it off and preventing fuel flow into the tank. A toggle switch with OFF, ON and momentary TEST functions is the operator's control over the station.
Specifications:
Level Ranges: 6 inches to 7 ft
Switches Adjustable: 0.5 to 8.5” from tank
top
Materials of Construction: PVC, CPVC, Al, Brass, 316 SS, Buna-N
Mounting:
Sensor: 2 Inch NPT Screw Fitting
Control Station : Surface
Temperature Range: -40 to +65oC
Power: 12VDC 24 VDC
10 mm, 8000 mcd Amber Lamp & Sonalert Audible Alarm with Silence Button
10 Amp Solenoid Valve Shutoff
Barrier Screw Terminal Blocks
Enclosure: NEMA-4X
Engraved Nameplate with Instructions
Need more information?
Download brochure & spec sheet
| |
|